Traduciendo...
FF38

Hardware Reconfiguration Request

ABB · ACS560 Standard Control Program Firmware

¿Qué significa FF38 ?

The inverter type (e.g., sr0025_3) has been changed, typically at the factory or during drive implementation. This fault indicates that the new configuration needs to be validated before the drive can operate correctly, requiring a specific power-off sequence.

Causas comunes

  • Drive control board or power module replaced with a different model or firmware version.
  • Firmware update initiated but not fully validated or a mismatch detected.
  • Parameter backup/restore operation performed with a file from a different drive model or configuration.
  • Corruption of internal drive configuration memory requiring reinitialization.
  • Installation of an incompatible option card (e.g., I/O extension, communication module).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Confirm the model and firmware version of the installed control board and power module match the original specification.

  2. 2

    Perform a factory reset (e.g., P99-01 = 1) and then re-enter or reload parameters from a known good backup file.

  3. 3

    Verify all installed option cards (e.g., fieldbus module, I/O extension) are compatible with the drive model and firmware.

  4. 4

    Attempt to re-upload the correct firmware using the manufacturer's commissioning tool, ensuring checksum validation passes.

  5. 5

    If available, try swapping the control board with a known good, compatible spare, then attempt to power cycle the drive.

Ver todos los códigos en este manual (33)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: ABB ACS560 Standard Control Program Firmware