EF0
Option Card External Fault
Yaskawa · iQpump1000
What does EF0 mean?
An external fault condition is present, received from the PLC via an option card. Depending on parameter F6-03, this condition may either stop the drive (F6-03 ≠ 3, page 254) or allow it to continue running as a minor fault (F6-03 = 3, page 273). This indicates an external issue communicated to the drive.
Common Causes
- External fault signal received from the PLC via the option card
- Problem with the PLC program generating an unintended external fault signal
Repair Steps & Checklist
Click steps to track your progress.
- 1
Identify and remove the root cause of the external fault condition in the connected equipment or system.
- 2
Verify and if necessary, remove the external fault input signal originating from the PLC.
- 3
Review the PLC program for any logic errors that might be generating an incorrect external fault signal.
Verified technical data. Last updated: March 2026
Related Faults
Source: Yaskawa iQpump1000