TiM
Keypad Time Not Set
Yaskawa · GA500 Maintenance and Troubleshooting
What does TiM mean?
This fault indicates that the keypad contains a battery, but the date and time have not been configured. This prevents proper logging and timestamping of events, potentially hindering accurate troubleshooting later. This detection can be enabled/disabled via parameter o4-24.
Common Causes
- Real-time clock on the keypad has not been set or has lost its time.
- Battery backup for the keypad's clock is depleted.
- Keypad requires initial configuration of time and date.
- Internal fault with the keypad's timekeeping module.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Access the keypad settings and manually set the current date and time.
- 2
Verify parameter o4-24 [bAT Detection Selection] is configured as desired for keypad time detection.
- 3
Perform a Fault Reset to clear the fault once the time is set.
Verified technical data. Last updated: March 2026
Related Faults
Source: Yaskawa GA500 Maintenance and Troubleshooting