dWFL

DriveWorksEZ Fault

Yaskawa · GA500 Maintenance and Troubleshooting

What does dWFL mean?

This generic DriveWorksEZ fault indicates an issue within the user-programmed logic or configuration. It is not a drive hardware malfunction but a problem in the custom program that prevents normal drive functionality.

Common Causes

  • General programming error or misconfiguration within the DriveWorksEZ application.
  • Attempting to write to a read-only parameter from within the DriveWorksEZ program.
  • Incompatible DriveWorksEZ program version with the drive firmware version.
  • Logical conflict between two simultaneously active DriveWorksEZ logic blocks.
  • Improper sequencing of operations within the DriveWorksEZ program.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Upload the DriveWorksEZ program from the drive and perform a thorough syntax and logic check.

  2. 2

    2. Verify the DriveWorksEZ software version matches the drive's firmware version by checking the drive's firmware parameter (e.g., A1-01).

  3. 3

    3. Disable sections of the DriveWorksEZ program incrementally to isolate the faulty logic.

  4. 4

    4. Reset drive parameters to factory default using A1-03=2220 and reload only essential DriveWorksEZ blocks.

  5. 5

    5. Use the DriveWorksEZ monitor tool to observe the status of internal variables and logic conditions during execution.