EL
ErrorLib
Brands
|||
  1. Home
  2. Yaskawa
  3. A1000

Yaskawa A1000

1 fault code documented

oPE12

Energy Save ON

The energy savings feature was enabled while the Output Voltage PID function was also active. This condition typically arises when parameter b8-01 (Energy Save) is set to 'Enable' (1) at the same time parameter P1-08 (Output Voltage PID Select) is set to 'Enabled' (1), and the drive's control method (A1-02) is configured for V/f operation.

About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

Buy me a coffee ☕️