45

Option Board Type Mismatch

Vacon · NX Liquid-Cooled Drive

What does 45 mean?

An option board of a different or incorrect type has been detected in a slot. This indicates a hardware configuration mismatch between the inserted board and the expected or previously configured type. Subcodes S1-S5 specify the board type (Control, Control unit, Power board, Power unit, Adapter board & slot).

Common Causes

  • Installed option board is not recognized or incompatible.
  • Option board wiring or connection issue.
  • Incorrect option board type selected in parameters (P0450).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Reset the fault.

  2. 2

    Verify the type of option board installed against the required or configured type for that slot.

  3. 3

    Set the option board parameters again, ensuring they match the characteristics of the newly installed or corrected board.

Browse all codes in this manual (52)
Verified technical data. Last updated: March 2026

Related Faults

Source: Vacon NX Liquid-Cooled Drive