Option Board Removed (Slot E)
Vacon · 100 FLOW Application Guide
What does 385 mean?
An option board that was configured for slot E has been physically removed from the drive. This means any features or connections provided by this option board are currently inactive. This fault will remain until appropriate action is taken.
Common Causes
- The option board configured for Slot E (as indicated by parameter P5-05) has been physically removed.
- The option board was inadvertently removed and not re-installed in the correct Slot E.
- Improper seating of the option board in Slot E's connector due to incorrect alignment or insufficient insertion force.
- Failure of the drive's internal circuitry responsible for detecting option boards in Slot E.
Repair Steps & Checklist
Click steps to track your progress.
- 1
1. With the drive powered off, carefully remove and re-seat the option board into Slot E, ensuring it is fully inserted.
- 2
2. Confirm that parameter P5-05 is set to the correct option board type for Slot E.
- 3
3. Check for any physical obstructions or bent pins within Slot E's connector on the drive's main board.
- 4
4. If possible, perform a soft reset or fault acknowledgement from the drive's HMI after re-installing the board.
- 5
5. Consult the drive's wiring diagram to verify proper power supply to Slot E (if test points are accessible).