Power unit: Internal overtemperature
Siemens · DCM
What does A05003 mean?
This alarm signifies that the internal temperature within a chassis power unit has reached its alarm threshold. If the temperature increases by an additional 5 K, it will escalate to fault F30036, leading to a shutdown. It's crucial to address this to prevent potential damage and ensure continued operation.
Common Causes
- Restricted cooling airflow due to dust accumulation on heat sinks, blocked ventilation openings, or dirty air filters.
- Ambient temperature inside the control cabinet exceeding the drive's specified maximum operating temperature (e.g., above 50°C).
- Reduced performance or partial failure of an internal cooling fan (e.g., decreased RPM, bearing noise) leading to inadequate heat dissipation.
- Continuous operation at or above the drive's rated output current (P0307) for extended periods without sufficient cooling margin.
- Improper control cabinet design leading to re-circulation of hot air or insufficient overall cabinet ventilation.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Monitor the drive's internal temperature sensors (e.g., r0035 for IGBTs, r0036 for heat sink) via diagnostics.
- 2
Inspect and thoroughly clean the power unit's heat sink fins, air intake vents, and air filters using dry compressed air.
- 3
Verify the actual ambient temperature inside the control cabinet using a calibrated thermometer; improve cabinet ventilation if necessary.
- 4
Check the operating speed (e.g., r0032) and audible performance of the internal cooling fans for any signs of degradation.
- 5
Reduce the drive's output load (e.g., via P1082) or adjust application cycle times to lower average current (r0027).