F20.2

Supply voltage – overload fault

SEW Eurodrive · MOVIDRIVE system

What does F20.2 mean?

The current load on the 24 V standby supply voltage in the MOVIDRIVE® system is too high. This overcurrent causes the device's internal signal output to de-energize. Leaving this unresolved can lead to system instability, unexpected shutdowns, and potential damage to internal components from sustained overload.

Common Causes

  • External 24VDC load connected to standby supply (e.g., X10/X11) exceeding the drive's specified current limit.
  • Short circuit or ground fault in the external wiring connected to the drive's 24VDC output terminals.
  • Malfunctioning external sensor or actuator drawing excessive current from the 24VDC supply.
  • Internal fault within the drive's 24VDC power supply circuit due to component stress.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect all external loads from the 24VDC output terminals (e.g., X10/X11) and measure the current draw from each device individually.

  2. 2

    Measure the voltage at the 24VDC output terminals (e.g., X10/X11) with a multimeter to verify it is stable and within tolerance.

  3. 3

    With all external loads disconnected, measure the current flowing from the 24VDC output using an ammeter to check for internal drive leakage.

  4. 4

    Isolate sections of the 24VDC external wiring by disconnecting them segment by segment and re-applying power to identify short circuits or ground faults.

  5. 5

    Refer to the drive manual to verify the maximum permissible 24VDC output current and ensure connected loads are within limits.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026