Serial Link Failure
Schneider Electric · Altivar Machine ATV340 Programming
What does -SLF mean?
This fault occurs when communication is lost between the drive controller and its connected serial devices, such as a remote keypad display or a MODBUS master controller. This prevents external control, monitoring, or parameter adjustment of the drive, interrupting automated processes. The cause could be physical disconnection, incorrect settings, or device malfunction.
Common Causes
- Broken, loose, or improperly terminated communication cable (e.g., RS-485 A/B wires, Ethernet cable) between the drive and master device.
- Incorrect communication parameters (e.g., baud rate P6-01, parity P6-02, drive address P6-03) configured in the drive or the master controller.
- Excessive electrical noise or electromagnetic interference (EMI) disrupting the communication signal integrity.
- Faulty communication module or port on either the drive or the master device (e.g., PLC, HMI).
- Device address conflict on the communication bus, where multiple devices respond to the same address.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify physical communication cable integrity (e.g., check for cuts, bends) and ensure all connectors are securely seated.
- 2
Confirm all communication parameters (e.g., P6-01 baud rate, P6-02 parity, P6-03 drive address) match the master device settings precisely.
- 3
Check for proper termination resistors (e.g., 120 Ohm for RS-485) at both physical ends of the communication bus.
- 4
Measure communication signal levels (e.g., using an oscilloscope for RS-485) to detect noise or signal degradation.
- 5
Temporarily disconnect other devices from the communication bus to isolate potential address conflicts or faulty devices.