-SCF

Motor Short-Circuit

Schneider Electric · Altivar Machine ATV340 Programming

What does -SCF mean?

This fault indicates a short-circuit or ground fault has occurred at the output of the drive controller, either in the motor cables or within the motor itself. This is a critical fault that can severely damage the drive controller's output stage (IGBTs) if power is maintained. Immediate action is required to prevent component failure.

Common Causes

  • Insulation breakdown in motor power cables (U, V, W) due to abrasion, crushing, or chemical exposure, creating a phase-to-phase or phase-to-ground short.
  • Short-circuit between motor windings or a winding to the motor frame (ground fault) inside the motor stator due to winding degradation.
  • Water ingress into the motor terminal box or cable glands, creating a conductive path between phases or to ground.
  • Internal failure of drive output power components (e.g., IGBTs) causing a direct short at the output terminals.
  • Incorrect motor connection (e.g., delta configuration for a wye-configured motor) causing excessive current and a protective short-circuit trip.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect motor cables (U, V, W) from the drive output terminals (T1, T2, T3) before proceeding.

  2. 2

    Perform an insulation resistance test (megger) on each motor phase cable to ground and phase-to-phase. Test at 500VDC.

  3. 3

    Measure resistance between motor phases (U-V, V-W, W-U) using a multimeter at the motor terminal box. Expect balanced, low resistance readings.

  4. 4

    Measure resistance from each motor phase to the motor frame ground using a multimeter. Expect an open circuit (infinite resistance).

  5. 5

    If motor and cables test good, measure resistance between drive output terminals (T1, T2, T3) with power OFF. Expect high resistance (internal components).

Browse all codes in this manual (13)
Verified technical data. Last updated: March 2026

Related Faults

Source: Schneider Electric Altivar Machine ATV340 Programming