291

2nd Motor Free Setting V/f Frequency 7 Exceeds Upper Limit

Omron · MX2 Inverter

What does 291 mean?

For the second motor settings, this warning occurs when the seventh point of the free setting V/f curve (b112), which also acts as the maximum frequency in this mode, is set higher than the 2nd frequency upper limit (A261). This creates an inconsistent operational boundary for V/f control for the second motor, limiting the actual achievable frequency.

Common Causes

  • Parameter b112 (Free setting V/f curve frequency point 7) for the second motor is set higher than parameter A261 (2nd frequency upper limit).
  • The V/f curve's maximum frequency point (b112) is configured to exceed the allowed operational upper frequency for the second motor (A261).
  • Inconsistent parameter configuration where the free setting V/f curve attempts to command a frequency beyond the defined system limits for the second motor.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Read the current values of parameter b112 (Free setting V/f curve frequency point 7) and parameter A261 (2nd frequency upper limit).

  2. 2

    Adjust parameter b112 to be less than or equal to parameter A261, ensuring the V/f curve point respects the upper frequency limit.

  3. 3

    Alternatively, if a higher operational upper limit is required, increase A261 to a value greater than or equal to b112.

  4. 4

    Save all parameter changes to the drive's memory and perform an inverter power cycle.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults