086

Multi-step Speed References 1-15 Conflict with Jump Frequency

Omron · MX2 Inverter

What does 086 mean?

This warning indicates that one or more of the multi-step speed references (A021-A035) are set to a value that conflicts with a defined jump frequency range (A063/A065/A067 ± A064/A066/A068). Operating at such a speed can cause mechanical resonance in the machine, potentially leading to damage or instability.

Common Causes

  • One or more of A021-A035 (Multi-step Speed References) were configured to a frequency value that falls within a defined jump frequency band (e.g., A063 ± A064).
  • Jump frequency parameters (A063-A068) were configured such that one of the bands unintentionally overlaps with an active multi-step speed reference.
  • The intended operating frequency for a specific multi-step speed is within a range that needs to be avoided due to mechanical resonance in the system.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Access multi-step speed reference parameters A021 through A035 and the jump frequency parameters A063 (Jump Freq 1), A064 (Jump Freq 1 Width), A065 (Jump Freq 2), A066 (Jump Freq 2 Width), A067 (Jump Freq 3), A068 (Jump Freq 3 Width).

  2. 2

    Calculate the exact jump frequency bands (e.g., A063 minus A064 divided by 2 to A063 plus A064 divided by 2).

  3. 3

    Identify which specific multi-step speed references (A021-A035) fall within any of the defined jump frequency bands.

  4. 4

    For each conflicting multi-step speed reference, adjust its value to fall outside of all defined jump frequency bands.

  5. 5

    Alternatively, if the multi-step speed references cannot be changed, redefine the jump frequency parameters (A063-A068) to ensure their bands do not overlap with any critical multi-step speeds.

  6. 6

    Save the parameter changes and power cycle the drive. Then re-check the parameter values and test operation using all affected multi-step speed references.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults