E39
Compressor Discharge Temperature Sensor (THOD) Defective
Mitsubishi Electric · R410A Systems
What does E39 mean?
The compressor discharge temperature sensor (THOD) is defective (resistance is open circuit) or has a poor connection to the outdoor unit PCB. This prevents accurate monitoring and protection of compressor discharge temperature, risking compressor damage.
Common Causes
- Compressor discharge temperature sensor (THOD) failure.
- Wiring to the THOD sensor is damaged or disconnected.
- THOD sensor reading is erratic or out of range.
- Internal failure of the THOD sensor.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Measure the resistance of the THOD sensor at its leads — compare to a resistance-temperature chart if available.
- 2
Inspect the THOD sensor's connector on the outdoor unit PCB — verify it is securely seated and free from corrosion.
- 3
Check for damage to the sensor wiring between the sensor and the PCB using a multimeter for continuity.
Verified technical data. Last updated: March 2026