EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. FR-A800 Variable Speed Drive (Separated Converter)
  4. E.RET
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

Feedback·Support ErrorLib
E.RET

Retry count excess

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.RET mean?

This fault indicates that the FR-A800/A800 Plus Series drive has attempted to clear a previous fault and restart operation multiple times, as configured by auto-restart parameters, but has failed to do so within the allowed retry count. This points to a persistent underlying issue.

Common Causes

  • An underlying fault (e.g., overcurrent, overvoltage) that consistently reoccurs after each retry attempt.
  • Incorrect auto-restart parameter settings, such as too many retries or insufficient delay between retries.
  • External conditions that repeatedly trigger protective functions (e.g., intermittent power supply issues, unstable load).
  • A persistent mechanical problem that repeatedly causes motor overload.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Identify the original fault that triggered the retry attempts by checking the drive's fault history, as E.RET is a consequence of persistent issues.

  2. 2

    Address the root cause of the original fault based on its specific troubleshooting steps.

  3. 3

    Review parameters related to auto-restart (e.g., Pr.57 for automatic restart after instantaneous power failure) and adjust the retry count or delay if necessary.

  4. 4

    Monitor the drive and application conditions for stability, including input power and mechanical load, to detect intermittent issues.

  5. 5

    Temporarily disable the auto-restart function to prevent continuous retries and allow for focused troubleshooting of the primary fault.

Browse all codes in this manual (46)
Verified technical data. Last updated: April 2026

Related Faults

ALM4Output Short-Circuit DetectionE. 1Option FaultE. 13Internal Circuit Fault
Source: Mitsubishi Electric FR-A800 Variable Speed Drive (Separated Converter)
Open Manual (Page 60)Search more codes in this manual