EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. FR-A800 Variable Speed Drive (Separated Converter)
  4. E.PE6
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

Feedback·Support ErrorLib
E.PE6

Internal Storage Device Fault

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.PE6 mean?

This protective function activates if data corruption occurs in the FR-A800 inverter's internal storage device or if data writing fails, typically due to power-OFF during parameter operations. The fault can prevent normal operation and requires specific corrective actions depending on the faulty area indicated by Pr.890.

Common Causes

  • Power-OFF occurring during parameter write operations (e.g., parameter clear, copy, offline auto tuning, or batch write via FR Configurator2).
  • Data fault in the inverter's internal storage device due to unexpected events or degradation.
  • Faulty storage area within the inverter, identified by Pr.890 values (e.g., '1, 3, 5, 7' for non-parameter settings, '2, 3, 6, 7' for standard parameters, '4, 5, 6, 7' for communication parameters).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the read value of Pr.890 to identify the faulty area. If Pr.890 is '7' or smaller, proceed with the next step.

  2. 2

    Perform an 'All parameter clear' operation, then an inverter reset. Be prepared to reconfigure all previously changed parameters.

  3. 3

    Verify the stability of the power supply to the FR-A800 inverter and any connected control devices. Ensure no unexpected power interruptions occur.

  4. 4

    If the fault persists after performing 'All parameter clear' and reset, or if Pr.890 indicates '8' or higher, contact Mitsubishi Electric service for further diagnosis.

  5. 5

    Ensure parameter changes are performed with a stable power supply and avoid sudden power-offs during write operations.

Browse all codes in this manual (46)
Verified technical data. Last updated: April 2026

Related Faults

ALM4Output Short-Circuit DetectionE. 1Option FaultE. 13Internal Circuit Fault
Source: Mitsubishi Electric FR-A800 Variable Speed Drive (Separated Converter)
Open Manual (Page 138)Search more codes in this manual