EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. FR-A800 Variable Speed Drive (Separated Converter)
  4. E.PE
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

Feedback·Support ErrorLib
E.PE

Parameter storage device fault (control circuit board)

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.PE mean?

This fault indicates an issue with the non-volatile memory on the control circuit board of the FR-A800/A800 Plus Series drive, where drive parameters are stored. This can lead to loss of settings or an inability to store new parameters, affecting drive operation.

Common Causes

  • Corruption of parameter data due to electrical noise, transient events, or unexpected power interruptions.
  • Internal hardware fault of the control circuit board's memory component.
  • Attempted parameter write operations during unstable power conditions.
  • Firmware inconsistencies or corruption affecting parameter storage.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Attempt to re-initialize the parameters to default settings and then carefully re-enter all necessary application-specific parameters.

  2. 2

    Verify the stability of the control power supply (e.g., 24VDC at terminal +24).

  3. 3

    Try to upload parameters from the FR-A800/A800 Plus Series drive using FR Configurator2, and if successful, download a known good parameter set.

  4. 4

    Inspect the control circuit board for any visible damage or signs of overheating.

  5. 5

    If the fault persists after re-parameterization and power cycling, it may indicate an internal hardware failure of the control circuit board, requiring replacement.

Browse all codes in this manual (46)
Verified technical data. Last updated: April 2026

Related Faults

ALM4Output Short-Circuit DetectionE. 1Option FaultE. 13Internal Circuit Fault
Source: Mitsubishi Electric FR-A800 Variable Speed Drive (Separated Converter)
Open Manual (Page 60)Search more codes in this manual