Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)
This fault indicates an error in the FR-A800's brake sequence control. This typically involves the timing and operation of an external mechanical brake, which is critical for holding the load and safe operation.
Click steps to track your progress.
Verify the wiring of the mechanical brake and its control circuit for correct connections and continuity.
Check the mechanical operation of the brake. Ensure it engages and releases smoothly and completely.
Review the brake sequence parameters in the FR-A800 (e.g., Pr.1540 Brake opening current detection level, Pr.1541-Pr.1543 for timing settings) and adjust them as needed.
Measure the current/voltage to the brake coil to ensure it is receiving the correct command.
Ensure the motor is capable of holding the load at zero speed before the brake releases and after it engages, if direct brake control is used.