This fault specifically indicates an issue with a 4-20mA analog current input signal. The fault typically triggers if the input current drops below 4mA (e.g., 0mA), indicating a broken wire or sensor failure.
Click steps to track your progress.
Verify the wiring of the 4-20mA input signal to the FR-A800 (e.g., terminals 4, 5) for secure connections and continuity.
Measure the current in the 4-20mA loop at the FR-A800 terminals using an ammeter to confirm the signal presence and value.
Check the external sensor or transducer that generates the 4-20mA signal for proper operation and power supply.
Inspect the current loop wiring for any breaks, shorts, or high resistance connections.
Ensure that the analog input parameter settings in the FR-A800 (e.g., Pr.59 for analog input selection, scaling parameters) are correctly configured for 4-20mA input.