EL
ErrorLib
Brands
||
  1. Home
  2. Mitsubishi Electric
  3. FR-A800 Variable Speed Drive (Separated Converter)
  4. E.AIE
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

Feedback·Support ErrorLib
E.AIE

Analog Input Fault

Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)

What does E.AIE mean?

This fault indicates an issue with the analog input signal received by the FR-A800 inverter. This can affect speed reference, feedback, or other control signals dependent on analog input.

Common Causes

  • Disconnected, loose, or broken wiring for the analog input signal (e.g., terminals 2, 4, 5, B, C).
  • Out-of-range analog input signal (e.g., voltage exceeding 10VDC or current exceeding 20mA).
  • Faulty external device providing the analog signal (e.g., potentiometer, sensor, PLC analog output module).
  • Short circuit or ground fault in the analog input wiring.
  • Internal fault with the FR-A800's analog input circuit.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the wiring of the analog input terminals (e.g., 2, 4, 5, B, C) for secure connections and continuity.

  2. 2

    Measure the analog input voltage or current at the FR-A800 terminals using a multimeter to ensure it is within the specified range (e.g., 0-10VDC, 4-20mA).

  3. 3

    Check the external device providing the analog signal for proper operation and calibration.

  4. 4

    Inspect the analog input wiring for any signs of damage, short circuits, or ground faults.

  5. 5

    Ensure that the analog input parameter settings (e.g., Pr.73, Pr.74 for analog input scaling, Pr.59, Pr.128, Pr.129 for input selection) are correct for the application.

Browse all codes in this manual (46)
Verified technical data. Last updated: April 2026

Related Faults

ALM4Output Short-Circuit DetectionE. 1Option FaultE. 13Internal Circuit Fault
Source: Mitsubishi Electric FR-A800 Variable Speed Drive (Separated Converter)
Open Manual (Page 102)Search more codes in this manual