Mitsubishi Electric · FR-A800 Variable Speed Drive (Separated Converter)
This fault indicates an issue during the process of decelerating the motor to a stop or reversing its direction, where the FR-A800 detects unexpected rotation or an inability to control the deceleration as commanded.
Click steps to track your progress.
Check for any mechanical binding, excessive friction, or external forces acting on the motor or load that could impede deceleration.
Verify the deceleration time parameters (Pr.7, Pr.8) are set appropriately for the application's inertia and required stopping time.
Ensure the braking resistor and its connection are correct and have sufficient capacity for the application's regenerative energy.
Check the motor's ability to produce sufficient torque for deceleration. Inspect motor wiring and verify motor parameters.
If an encoder is used for speed feedback, verify its operation and correct installation, as inaccurate feedback can cause control issues during deceleration.