Lenze 8200 Series

163 fault codes documented

0011

OC1 Overcurrent in motor cable

An overcurrent (Ia > 2.25 x IN) has occurred in the motor cable, detected by hardware monitoring. This can be caused by a short circuit in the motor cable, excessive capacitive charging current of the motor cable, or acceleration/deceleration times that are too short for the load. It can also indicate a missing mains phase or an encoder wiring issue.

011

OC1

A short circuit has occurred in the motor cable, or there is excessive capacitive charging current if the motor cable is too long or has high capacitance. This can lead to drive tripping and potential damage.

0012

OC2 Motor cable earth fault

One of the motor phases has made contact with earth, indicating an insulation fault in the motor cable. This condition poses a risk of electrical shock and further equipment damage.

012

OC2

One of the motor phases has made contact with earth (ground), indicating an earth fault. This suggests an insulation breakdown in the motor cable or the motor windings.

0013

OC3 Overload during acceleration

This fault indicates an overload condition during acceleration due to acceleration or deceleration times (C0012, C0013, C0105) that are too short relative to the connected load. The current controller is likely reaching its limits frequently.

0015

OC5 I x t overload

This fault occurs due to frequent and excessively long acceleration processes with overcurrent, or continuous overload where the motor current (Imotor) exceeds 1.05 times the rated current (Irx). A device utilization (C0064) exceeding 100% releases a warning for this condition. The drive dimensioning may be insufficient for the application's duty cycle.

015

OC5

The drive is experiencing an I x t overload, characterized by frequent and excessively long acceleration phases with overcurrent, or continuous overload where Imotor > 1.05 x Irx. This indicates that the drive is undersized for the application.

0016

OC6 I²xt overload

This fault is triggered by frequent and excessively long acceleration processes with motor overcurrent, or permanent motor overload where the motor current (Imotor) exceeds the rated motor current (Irmotor). The drive or motor dimensioning may be inadequate for the application's continuous or peak load requirements.

016

OC6

The drive is experiencing an I²xt overload, characterized by frequent and excessively long acceleration processes with motor overcurrent, or permanent motor overload where Imotor > Irmotor. This signals a prolonged motor overload condition.

018

I²xt overload advance warning

This is an advance warning for an I²xt overload, indicating frequent and excessively long acceleration processes with motor overcurrent, or permanent motor overload where Imotor > Irmotor. It signals an impending trip condition if conditions do not change.

032

LP1

A current-carrying motor phase has failed, or the current limit value is set too low. This can lead to irregular motor operation, reduced performance, or motor damage.

32

Fieldbus Motor Phase Failure (TRIP)

The drive has detected a motor phase failure and has triggered a TRIP fault, indicated via the fieldbus interface. This means one or more motor phases are inactive or drawing insufficient current. The fault prevents further operation and requires investigation of motor connections or parameters to avoid motor or drive damage.

0050

OH Heatsink temperature > +90°C

The heatsink temperature has exceeded +90°C (or >85°C as an earlier warning threshold, C0061). This can be caused by ambient temperatures (Tu) above +40°C or +50°C, a dirty heatsink impeding airflow, or an incorrect mounting position preventing adequate ventilation.

050

OH

The heatsink temperature has exceeded +90°C. This is often caused by an ambient temperature greater than +40°C or +50°C, a dirty heatsink, or an incorrect mounting position, leading to potential overheating.

065

CE4

The controller has entered a BUS-OFF state on the system bus (CAN) due to receiving too many faulty telegrams, leading to disconnection from the bus. This indicates a severe communication breakdown.

066

CE5

A time-out has occurred on the system bus (CAN) during remote parameterization (C0370, C0371), indicating a communication error of the gateway function. The slave device did not respond within the communication monitoring time.

070

U15

The internal 15V voltage supply is experiencing an undervoltage condition. This affects the internal control electronics and can prevent proper device operation.

0071

CCr (System failure)

A system failure has occurred, likely due to strong interference injection on control cables or ground/earth loops in the wiring. This indicates an electrical noise or grounding issue affecting the controller's stability.

071

CCr

A system failure has occurred due to strong interference injection on the control cables. This can be caused by inadequate shielding or ground/earth loops in the wiring, leading to unstable operation.

0072

PR1 (Checksum error in parameter set 1)

A checksum error has been detected in parameter set 1. This fault can arise from issues during parameter set loading, interruption during transfer via keypad, or incompatibility between stored parameters and the loaded software version.

072

PR1

A checksum error was detected in parameter set 1 during loading or transfer via the keypad. This indicates a fault in the parameter data or incompatibility with the loaded software version. The Lenze default settings are loaded automatically.

0073

PR2 (Checksum error in parameter set 2)

A checksum error has been detected in parameter set 2. This fault can arise from issues during parameter set loading, interruption during transfer via keypad, or incompatibility between stored parameters and the loaded software version.

073

PR2

A checksum error was detected in parameter set 2 during loading or transfer via the keypad. This indicates a fault in the parameter data or incompatibility with the loaded software version. The Lenze default settings are loaded automatically.

0074

PEr (Program error)

An error has occurred in the program flow of the device. This indicates an internal software issue within the controller's operating system, potentially requiring a software analysis by the manufacturer.

074

PEr

An error has occurred in the program flow, indicating an internal software issue within the device. This may lead to unexpected behavior or system stoppage.

0075

PR0 (Error in parameter set)

An error has occurred in the parameter set, possibly due to an operating system software update. The Lenze default settings (C0003 = 1) are automatically loaded as a result of this fault.

075

PR0

An error exists in the parameter set, often triggered after an operating system software update. The device automatically loads the Lenze default settings.

0077

PR3 (Checksum error in parameter set 3)

A checksum error has been detected in parameter set 3, indicating a fault during loading or an interruption during transfer via the keypad. This can also occur if saved parameters are incompatible with the loaded software version.

077

PR3

A checksum error was detected in parameter set 3 during loading or transfer via the keypad. This indicates a fault in the parameter data or incompatibility with the loaded software version. The Lenze default settings are loaded automatically.

0078

PR4 (Checksum error in parameter set 4)

A checksum error has been detected in parameter set 4, indicating a fault during loading or an interruption during transfer via the keypad. This can also occur if saved parameters are incompatible with the loaded software version.

078

PR4

A checksum error was detected in parameter set 4 during loading or transfer via the keypad. This indicates a fault in the parameter data or incompatibility with the loaded software version. The Lenze default settings are loaded automatically.

0079

PI (Fault during parameter initialisation)

An error was detected during parameter set transfer between two devices, or the parameter set does not match the controller (e.g., higher-power controller data transferred to lower-power). This prevents proper device initialization.

079

PI

A fault occurred during parameter initialization, likely during parameter set transfer between two devices, or because the parameter set does not match the controller (e.g., from a higher-power controller to a lower-power one).

080

PR6

The device has reached the maximum allowed number of user codes. This prevents the creation or storage of additional user-defined settings.

082

Sd2

A resolver error has occurred at terminal X7, typically indicating an interrupted resolver cable. This prevents accurate position feedback.

083

Sd3

An encoder error has occurred at terminal X9, typically due to an interrupted encoder cable or pin X9/8 not being connected. This can lead to incorrect or no position feedback.

085

Sd5

An encoder error has occurred at X6/1 and X6/2 (when C0034 = 1), indicated by a current signal less than 2mA at these terminals. This suggests an open circuit or a faulty current signal encoder.

086

Sd6

The encoder for detecting motor temperature at X7 or X8 is indicating undefined values. This suggests a problem with the temperature sensor, its cable, or connection.

087

Sd7

An initialization error occurred at the absolute value encoder at X8, or the encoder electronics are defective. This can result from a loose cable, an open circuit, an incorrect encoder type, or failure during rotor position adjustment.

088

SinCos encoder at X8 sends inconsistent data.

The SinCos encoder at X8 is sending inconsistent data, indicating damaged internal tracks or high interference on the encoder cable. It could also mean the encoder is not transmitting data due to an open circuit, an incorrect encoder type, or a defective sensor.

089

PL

The rotor position adjustment was canceled, possibly due to an Sd7 or Sd8 error occurring during the adjustment with an absolute value encoder. This error is saved with mains failure protection.

091

EEr

External monitoring has been triggered via the DCTRL input. A digital signal assigned to the TRIP-SET function has been activated.

0105

H05 (Internal fault (memory))

An internal fault related to the controller's memory has been detected. This indicates a critical hardware or firmware issue within the drive itself.

105

H05

An internal fault related to the device's memory has occurred. This typically indicates a hardware issue that requires specialized attention.

0107

H07 (Internal fault (power stage))

During the controller's initialization phase, an incorrect power stage was detected. This implies a critical internal hardware mismatch or failure within the power electronics.

107

H07

An internal fault related to the power stage has occurred. During the initialisation of the controller, an incorrect power stage was detected, indicating a serious internal hardware issue.

110

H10

The sensor for detecting the heatsink temperature is indicating undefined values. This suggests a fault with the sensor or its connection, leading to unreliable temperature monitoring.

111

H11

The temperature sensor inside the controller is indicating undefined values. This suggests a fault with the sensor or its connection, leading to unreliable internal temperature monitoring.

0140

ID1 (Error during motor data identification)

An error occurred during the motor data identification process. This can be caused by a disconnected motor, excessively high stator resistance, or the controller being externally inhibited during the identification sequence.

0141

ID2 (Error during motor data identification - motor too small)

An error occurred during motor data identification, indicating the connected motor may be too small for the drive. This can also be caused by an externally inhibited controller during the identification process, preventing proper measurement.

151

Error "negative limit switch".

The negative limit switch has been reached, preventing further movement of the drive in the negative direction. This is a safety mechanism to prevent overtravel.

152

Error "positive limit switch".

The positive limit switch has been reached, preventing further movement of the drive in the positive direction. This is a safety mechanism to prevent overtravel.

153

Following error

The angle difference between the set position and the actual position is larger than the following error limit set under parameter C0255. This can also indicate the drive cannot follow the digital frequency due to reaching its Imax limit, suggesting insufficient drive dimensioning.

154

Error "negative position limit".

The negative position limit (C1224) was not reached, potentially due to incorrect position targets or issues with the 'set function position value'. This can prevent the drive from reaching its intended negative travel extreme.

155

Error "positive position limit".

The positive position limit (C1223) was exceeded, potentially due to incorrect position targets or issues with the 'set function position value'. This can cause the drive to overtravel its intended positive extreme.

156

No reference.

The reference point for the drive is not known. In absolute positioning mode, homing was not performed before the first positioning command, which is essential for establishing a known position.

157

Parameter set mode is absolute instead of relative.

An absolute parameter set (C1311) was performed or is active during relative positioning (position mode C1210). This mismatch in positioning modes prevents correct operation.

158

Error "actual reference dimension offset".

The actual reference dimension offset (C1226) is outside the defined position limits. This indicates an error with the program function 'set position value' or incorrect limit settings.

159

Error in positioning program.

The positioning program contains impermissible programming. Specifically, a parameter set with a final speed must be followed by a parameter set with positioning, and it is not permissible to wait for input at that stage.

162

Error in the range of the encoder.

The traversing range of the absolute encoder has been exceeded. This means the physical travel of the drive has gone beyond the measurement capabilities of the installed encoder.

182

Fieldbus Motor Phase Failure (Warning)

The drive has detected a motor phase failure and issued a Warning, indicated via the fieldbus interface. This means one or more motor phases are inactive or drawing insufficient current, but the drive may still be operating or preparing to trip. It requires prompt attention to prevent potential motor or drive damage if the condition persists.

0200

NMAX Maximum speed exceeded

The motor speed has exceeded the maximum limit defined in parameter C0596. This indicates an overspeed condition potentially due to incorrect parameter settings, external load conditions, or control system malfunction.

0209

float Sys-T

A float error, such as division by zero, has occurred in the system task (ID 0) during real number calculations. This indicates an issue within the program code's arithmetic operations, leading to an imprecise or undefined result.

0210

float Cycl.-T

A float error, such as division by zero, has occurred in the cyclic task (PLC_PRG ID 1) during real number calculations. This indicates an issue within the PLC program's arithmetic operations that impacts the cyclic execution.

0211

float Task1

A float error, such as division by zero, has occurred in task 1 (ID 2) during real number calculations. This indicates an issue within the program code specific to task 1's arithmetic operations.

0218

float Task8

A float error, such as division by zero, has occurred in task 8 (ID 9) during real number calculations. This indicates an issue within the program code specific to task 8's arithmetic operations.

0219

overrun Cyc.-T

The cyclic task (PLC_PRG ID 1) has exceeded its allocated monitoring time. This indicates that the task processing duration is longer than the set monitoring time, potentially due to complex or lengthy program parts.

0220

noT-Fkt Credit

The controller lacks the necessary technology units to execute a loaded program containing technology functions. This indicates a mismatch between the program's requirements and the controller's hardware capabilities.

0230

No Program

No PLC program has been loaded into the controller's memory. The controller is unable to execute any programmed logic or control functions without a loaded program.

0231

Unallowed Lib

The PLC program attempted to call a library function that is not supported by the current controller hardware or firmware. This means a required hardware component might be missing, or the function is incompatible with the controller variant.

0232

NoCam Data

Motion profiles (CAM data) are not available in the controller's memory, despite functions from the `LenzeCamControl.lib` library being called. This prevents motion control functions from operating correctly, potentially due to incorrect project setup or a reset.

252

AddData DlErr Error during FLASH memory access

An error occurred when downloading data into the FLASH memory. This can be caused by a time-out, transmission error, or a mains failure during the data transfer process, resulting in incomplete or corrupt data.

260

Err Node Guard "Life guarding event"

The controller, configured as a CAN slave, did not receive a 'Node Guarding' telegram from the CAN master within the configured 'Node Life Time'. This indicates a loss of communication supervision on the CAN bus.

1020

OU

An overvoltage condition exists in the DC bus, where the DC bus voltage is higher than the value set in parameter C0173. This is typically caused by excessive braking energy being fed back to the bus.

1030

LU

An undervoltage condition exists in the DC bus, where the DC bus voltage is lower than the value specified in parameter C0173. This typically indicates insufficient input power to the drive.

2020

OU Overvoltage in the DC bus

The DC bus voltage has exceeded the switch-off threshold OU (e.g., 770V for <400V mains with C0173=0) as specified by parameter C0173, indicating excessive braking energy. The pulse inhibit is set, and a delay time (C0912) starts until the voltage falls below the switch-on threshold OU (e.g., 755V for <400V mains).

CCr

System failure

This fault indicates a system failure caused by strong interference injection on the control cables or ground/earth loops in the wiring. Such interference can lead to unpredictable system behavior and instability.

CE0

Automation interface (AIF) communication error

Faulty transfer of control commands has occurred via the Automation Interface (AIF). This is often due to a loose communication module or keypad XT connection, disrupting essential command signals.

CE1

CAN1_IN communication error

The CAN1_IN object is receiving faulty data or communication is interrupted. This is likely caused by wiring issues at X4, a faulty sender, or an insufficient monitoring time for the communication, leading to unreliable data exchange.

CE2

CAN2_IN communication error

The CAN2_IN object is receiving faulty data or communication is interrupted. This is likely caused by wiring issues at X4, a faulty sender, or an insufficient monitoring time for the communication, leading to unreliable data exchange.

CE3

CAN3_IN communication error

The CAN3_IN object is receiving faulty data or communication is interrupted. This is likely caused by wiring issues at X4, a faulty sender, or an insufficient monitoring time for the communication, leading to unreliable data exchange.

CE4

BUS-OFF state of system bus (CAN)

The controller has received too many faulty telegrams via the system bus (CAN) and has disconnected from the bus. This indicates a severe communication issue on the CAN network, preventing data exchange.

ce5

CAN Time-Out

A CAN communication timeout has occurred. This could be due to a slave device not responding during remote parameterization (C0370), incorrect parameter set changeover configuration with application I/O, or an internal error with a module on the FIF. A communication timeout means commands or data are not being exchanged, leading to operational halts or incorrect behavior.

ce6

CAN Module Warning/Bus-Off

The CAN function module on the FIF has reported a 'Warning' or 'Bus-Off' status, indicating underlying communication issues. This often points to problems with bus termination, cable shielding, PE connection, or an overloaded bus. While 'Warning' might allow limited operation, 'Bus-Off' will completely halt communication.

ce7

CAN Remote Parameterization Error

A communication error has occurred during remote parameterization via the system bus (C0370), typically because a node is unresponsive or unavailable. This can also be caused by incorrect parameter set changeover configuration with application I/O. Such errors prevent remote configuration and control of the drive.

Earth fault

Earth fault

The drive system includes protective measures against earth faults, though to a limited extent, as per EN 61800-5-1. This fault indicates current leakage to ground, posing risks of electrical shock and equipment damage. Fault acknowledgement is necessary to clear this condition and resume operation.

EEr

External Fault (TRIP-SET)

An external disturbance has been detected, activating a digital signal assigned to the TRIP-SET function (DCTRL1-TRIP-SET). This typically results from a LOW level at the signal source for this function, causing the controller to inhibit. Ignoring this can lead to system shutdown and operational delays.

ErP

Keypad/Device Communication Abort

A communication abort has occurred between the keypad and the standard device (e.g., fault codes ErP0 through ErP19), indicating a failure in data exchange. The specific cause can vary. This prevents proper interaction with the device via the keypad and requires expert assistance for diagnosis.

FAn1

Fan Failure

The cooling fan, particularly in 8200 motec controllers (3...7.5 kW), has either failed or is disconnected. This condition can lead to the controller overheating, potentially causing thermal shutdown and reducing the lifespan of internal components if not addressed promptly.

GLOBAL DRIVE INIT

Initialization or Communication Error

This status indicates an initialization error or a communication error between the keypad and the controller. It signifies that the drive controller is unable to properly start up or establish communication with its human-machine interface.

H05

Internal Fault

An internal hardware or software fault has been detected within the controller, indicating a critical system malfunction. This issue cannot be resolved through standard troubleshooting and requires specialized attention to prevent potential damage or system instability.

H07

Internal fault (power stage)

During the initialisation of the controller, an incorrect power stage was detected. This signifies a critical internal hardware issue related to the power conversion circuitry.

H10

Heatsink temperature sensor error

The sensor for detecting the heatsink temperature is indicating undefined values. This prevents accurate monitoring of the heatsink's thermal status, potentially leading to overheating if not addressed.

H11

Internal controller temperature sensor error

The sensor for detecting the internal temperature of the controller is indicating undefined values. This prevents accurate monitoring of the internal component temperature, risking damage from overheating.

id1

Parameter Identification Fault

The motor parameter identification process has failed, most likely because the motor is not properly connected to the drive. Incorrect parameter identification can lead to suboptimal motor control, instability, and potential damage to both the motor and the drive if not resolved.

LP1

Motor Phase Interruption Monitoring

Monitoring of motor phases (LP1) does not respond to an interrupted motor phase, even if C0597 = 0 or 2, because the MLP1 function block is not entered into the processing table. This means an interrupted motor phase will not be detected.

LU

Undervoltage in the DC bus

The DC bus voltage is lower than the value specified in C0173. This indicates insufficient input power to the drive, potentially due to issues with the mains voltage or supply cabling, preventing proper drive operation.

Motor overtemperature

Motor Overtemperature

The drive system provides protection against motor overtemperature, specifically monitored using an I²xt-monitoring function. This feature safeguards the motor from thermal damage caused by prolonged overload or inadequate cooling, triggering a fault when internal temperature limits are exceeded.

nErr

Speed control error

The motor speed is out of the tolerance margin defined by C0576. This typically occurs due to an excessively high active load (e.g., in hoists) or mechanical blockades, preventing the drive from achieving the commanded speed.

NMAX

Maximum system speed exceeded

The maximum system speed, set by C0596, has been exceeded. This can be caused by an active load that is too high, the drive not being speed-controlled, or an excessively limited torque, leading to overspeed conditions.

OC1

Output Short Circuit

A short circuit has been detected on the drive's output, possibly in the motor, motor cables, or brake resistor circuit. Excessive capacitive charging current from long or high-capacitance motor cables can also falsely trigger this fault. An unresolved short circuit poses a severe risk of damage to the drive's output stage.

OC2

Motor cable earth fault

One of the motor phases has earth contact, indicating an insulation fault in the motor cable or motor windings. This presents a safety risk and can cause drive damage.

OC3

Controller Overload (Acceleration)

The controller has experienced an overload condition during acceleration, possibly due to an acceleration time (C0012) that is too short, an improperly dimensioned drive, or issues with the motor/cabling like a defective motor cable or interturn fault. Persistent overloading can lead to drive component degradation and premature failure.

OC4

Controller Overload (Deceleration)

The controller has overloaded during deceleration, often because the deceleration time (C0013) is set too short or the external brake resistor is inadequately dimensioned. Excessive regenerative energy not properly dissipated can damage the drive's DC bus components and lead to overvoltage faults.

OC5

Controller Overload (Steady-State)

The controller is experiencing frequent or prolonged overload periods during steady-state operation, indicating the drive is undersized for the continuous load. Continuous operation beyond the drive's rated capacity will lead to overheating and significantly reduce its lifespan, potentially causing premature failure.

OC6

Motor Overload (I²t)

The motor has exceeded its thermal overload limit (I²t model), caused by excessive continuous current or frequent/prolonged acceleration cycles. This indicates the motor is either undersized for the application, or the drive parameters are not correctly configured. Continued operation under overload conditions will severely damage the motor windings.

OC8

I²xt overload advance warning

This is an advance warning for a potential I²xt overload, indicating frequent and prolonged acceleration processes with motor overcurrent or permanent motor overload with Imotor > Irmotor. It suggests that conditions are approaching a trip threshold.

OH

Heatsink Overtemperature Warning

The drive has detected a heatsink overtemperature condition. This is a warning that indicates the heatsink temperature has exceeded its normal operating range, but the drive continues to operate in a controlled manner.

OH3

Motor Overtemperature (PTC TRIP)

The motor's PTC thermistor has detected an overtemperature condition, triggering a TRIP fault. This is usually caused by the motor operating under impermissible high currents or frequent/long acceleration processes, or simply if the PTC sensor is not connected while monitoring is active (C0119 = 1 or 4). Continued motor operation in an overtemperature state will lead to severe winding damage and premature motor failure.

OH4

Controller Overtemperature (Internal)

The controller's internal temperature has exceeded its safe operating limit. This indicates that the controller is experiencing excessive load, has insufficient cooling, or its internal fan is failing. Sustained internal overtemperature will lead to derating, thermal shutdown, and reduced lifespan of internal components.

OH7

Motor overtemperature (C0121)

The motor temperature, detected via resolver or incremental encoder, has exceeded the threshold set in C0121. This indicates thermal overload from impermissible continuous current, frequent/prolonged acceleration processes, or the C0121 value being set too low.

OH8

Motor overtemperature (T1/T2)

The motor temperature, measured via inputs T1 and T2, is too high. This signifies thermal overload due to impermissible continuous current or frequent/prolonged acceleration processes. It can also occur if terminals T1 and T2 are not connected to a PTC/temperature contact.

OH51

PTC Monitoring

The drive has triggered the PTC monitoring function. This indicates that the Positive Temperature Coefficient (PTC) thermistor, likely in the motor, has exceeded its threshold temperature, signifying an overtemperature condition. The drive continues to operate in a controlled manner.

OU

Overvoltage during DC-injection braking

An overvoltage (OU) TRIP occurs if, during DC-injection braking (GSB) at high motor speeds, the residual voltage from magnetism and high speed generates an excessive motor current. This can lead to overvoltage due to the drive's attempt to reduce magnetization when the pulse inhibit (DCTRL-IMP) is too short.

OUE

DC Bus Overvoltage (Braking/Earth Leakage)

An overvoltage condition has occurred, specifically related to braking operations or an earth leakage at the motor end. During braking, insufficient deceleration time or an undersized/defective brake resistor can cause this. An earth leakage in the motor or cable also contributes. This fault indicates high stress on the drive's DC bus, potentially leading to component failure.

P03

Following error

The angle difference between the set and actual position is larger than the following error limit set under C0255. This indicates that the drive cannot accurately follow the commanded position or speed, possibly due to insufficient torque or excessive load.

P13

Angle overrun

The phase controller limit has been reached, meaning the drive cannot follow the digital frequency due to hitting its Imax limit. This indicates the drive is being commanded beyond its current capability, potentially causing instability.

P16

CAN sync telegram transfer error

The sync telegram from the master (PLC) is out of sync cycle or not received, indicating a communication issue. This can also occur if the controller is enabled too fast, before the sync telegrams are stable.

P19

Input values at X9 are limited

The function block DFIN is limiting the input values at X9, which causes a loss of increments. This suggests an issue with the digital frequency connection or a mismatch in master/slave settings, affecting precise control.

PEr

Program error

An error has been detected in the program flow of the device. This signifies an internal software issue that prevents normal operation.

PI

Fault during parameter initialisation

An error was detected during the parameter set transfer between two devices, or the parameter set does not match the controller (e.g., if data was transferred from a higher-power controller to a lower-power controller). This can lead to incorrect drive configuration.

PL

Error during rotor position adjustment

The rotor position adjustment process was cancelled, often because an Sd7 or Sd8 error occurred during adjustment with an absolute value encoder. Without a successfully executed rotor position adjustment, the drive may carry out uncontrolled movements.

Pr

Defective All Parameter Sets

All parameter sets within the controller have become defective, often due to an interrupted or faulty parameter transfer from the keypad. This critical issue prevents the drive from operating correctly as its configuration is lost or corrupted. Operating with corrupted parameters can lead to unpredictable behavior and potential damage.

PR0

Error in parameter set

This error occurs when the operating system software has been updated and requires the storage of the Lenze setting to ensure compatibility. This typically happens after a firmware upgrade.

PR1

Checksum error in parameter set 1

A fault occurred when loading parameter set 1, which could be due to an interruption during transmission via the keypad or incompatibility between the stored parameters and the loaded software version. The Lenze setting is loaded automatically.

Pr2

Defective Parameter Set 2

Parameter set 2 within the controller has become defective, likely due to an interrupted or faulty transfer from the keypad. This indicates a corruption in a specific configuration set, which can prevent proper drive operation when that set is active. Operating with corrupted parameters can lead to unpredictable behavior.

Pr3

Defective Parameter Set 3

Parameter set 3 within the controller has become defective, likely due to an interrupted or faulty transfer from the keypad. This indicates a corruption in a specific configuration set, which can prevent proper drive operation when that set is active. Operating with corrupted parameters can lead to unpredictable behavior.

Pr4

Defective Parameter Set 4

Parameter set 4 within the controller has become defective, likely due to an interrupted or faulty transfer from the keypad. This indicates a corruption in a specific configuration set, which can prevent proper drive operation when that set is active. Operating with corrupted parameters can lead to unpredictable behavior.

Pr5

Internal Fault (EEPROM)

An internal fault related to the EEPROM (Electrically Erasable Programmable Read-Only Memory) has been detected, indicating a defect in the controller's non-volatile memory. This is a critical hardware failure that can lead to data loss and system malfunction. This fault requires manufacturer intervention.

Pt5

Parameter Transfer Time Error

A time error occurred during parameter set transfer, meaning the data flow from the keypad or PC was interrupted (e.g., keypad removed). This incomplete transfer can leave parameters in an undefined state, preventing correct operation. Operating with partially transferred parameters can cause erratic and dangerous behavior.

rSt

Auto-TRIP Reset Error (Counter Exceeded)

This fault indicates that the controller has attempted and failed to perform more than eight automatic TRIP resets within a 10-minute period. It signifies a persistent underlying fault condition that repeatedly triggers and attempts to reset, but the root cause is not being resolved. Ignoring this means an underlying problem is not being addressed, leading to repeated shutdowns and potential drive wear.

Sd2

Resolver error at X7

The resolver cable connected to X7 is interrupted, or the resolver itself is faulty. This prevents accurate motor position feedback, which is crucial for precise motor control.

Sd3

Encoder error at X9

The encoder cable connected to X9 is interrupted, or pin X9/8 is not connected (input signal 'Lamp Control' at X9/8 is LOW). This leads to a loss of encoder feedback, which can cause uncontrolled drive movements if not addressed.

Sd5

Encoder error at X6/1 and X6/2

The current signal at analog input X6/1 and X6/2 is less than 2mA, indicating an issue with the encoder or its wiring. This monitoring is only possible if C0034 = 1, and its failure means loss of accurate position feedback.

Sd6

Motor temperature sensor error

The encoder for detecting the motor temperature at X7 or X8 is indicating undefined values. This prevents proper motor thermal protection and could lead to motor damage due to overheating.

Sd7

Absolute value encoder initialisation error at X8

The absolute value encoder at X8 has an initialisation error, is defective, or is not sending data. This may also occur if the encoder constant (C0420) for C0025=309 is altered. An uninitialised encoder can lead to uncontrolled drive movements.

Sd8

SinCos encoder error at X8

The SinCos encoder at X8 is sending inconsistent data, indicating damaged tracks, high interference levels on the cable, or an open circuit. It could also be due to an incorrect encoder type or improperly set supply voltage.

Short circuit

Short circuit

The drive system includes protective measures against short circuits, though to a limited extent, as per EN 61800-5-1. This fault indicates an abnormal current path, potentially causing excessive current flow and damage to internal components or connected wiring. Fault acknowledgement is necessary to clear this condition and resume operation.

x018

OC8 I²xt overload advance warning

This is an advance warning indicating frequent and excessively long acceleration processes with motor overcurrent, or permanent motor overload where the motor current (Imotor) exceeds the rated motor current (Irmotor). This condition suggests that the drive or motor dimensioning may be inadequate, and continuous operation without addressing it could lead to an OC6 trip. This warning is managed by parameter C0606.

x032

LP1 Motor phase failure

One of the current-carrying motor phases has failed. This monitoring function is primarily for asynchronous motors and requires the MLP1 function block to be entered in C0465. Possible causes include a faulty motor, a damaged motor cable, or a current limit value (C0599) set too low. The monitoring can be switched off via C0597.

x053

OH3 Motor temperature > +150°C threshold

The motor temperature has exceeded the +150°C threshold, detected via resolver or incremental value encoder (e.g., KTY sensor at X8/5, X8/8). This indicates the motor is thermally overloaded due to impermissible continuous current or frequent/long acceleration processes. This monitoring can be switched off via C0583.

x054

OH4 Heatsink temperature > C0122

The heatsink temperature has exceeded the specific threshold value set in parameter C0122. This is an advance warning for heatsink overheating, which can be caused by high ambient temperatures (Tu > +40°C or +50°C), a dirty heatsink, or an incorrect mounting position. This monitoring can be switched off via C0582.

x057

OH7 Motor temperature > C0121

The motor temperature has exceeded the specific threshold value set in parameter C0121, detected via resolver or incremental value encoder. This indicates the motor is thermally overloaded due to impermissible continuous current or frequent/long acceleration processes. This is an advance warning for motor overheating. This monitoring can be switched off via C0584.

x058

OH8 Motor temperature via inputs T1 and T2 is too high

The motor temperature is too high, detected by a PTC or temperature contact connected to terminals T1 and T2. This indicates motor thermal overload due to impermissible continuous current or frequent/long acceleration processes. The fault can also occur if terminals T1 and T2 are not correctly connected to a temperature sensor. This monitoring can be switched off via C0585.

x061

CE0 Communication error on the automation interface (AIF)

A communication error has occurred on the automation interface (AIF). This indicates a problem with the physical communication link, its configuration, or the communication master. This error is managed by parameter C0126.

x062

CE1 Communication error at process data input object CAN1_IN

A communication error has occurred with the process data input object CAN1_IN. This can be due to issues with the CAN bus, wiring, or incorrect data configuration. The monitoring time for this communication channel can be set with parameter C0357/1.

x063

CE2 Communication error at process data input object CAN2_IN

A communication error has occurred with the process data input object CAN2_IN. This can be due to issues with the CAN bus, wiring, or incorrect data configuration. The monitoring time for this communication channel can be set with parameter C0357/2.

x064

CE3 Communication error at process data input object CAN3_IN

A communication error has occurred with the process data input object CAN3_IN. This can be due to issues with the CAN bus, wiring, or incorrect data configuration. The monitoring time for this communication channel can be set with parameter C0357/3.

x065

CE4 BUS-OFF state of the system bus (CAN)

The system bus (CAN) has entered a BUS-OFF state due to an excessive number of faulty telegrams. This indicates a severe and persistent communication problem on the CAN network, which is configured via parameter C0595.

x083

Sd3 Interruption of the digital frequency coupling

The input signal 'Lamp Control' at terminal X9/8 is LOW, indicating an interruption of the digital frequency coupling. If the response (C0587) is set to 'Warning' (2), continued operation without addressing this fault can potentially damage the drive.

x085

Sd5 Analog input current < 2 mA

The input current at analog input X6/1 or X6/2 has fallen below 2 mA. This monitoring function is only active if parameter C0034 is set to 1, indicating a low current condition on the analog input.

x086

Sd6 Thermal sensor error at motor (X7 or X8)

An error has been detected with the thermal sensor connected to the motor inputs X7 or X8. This indicates a malfunction of the sensor itself or an issue with its wiring, preventing accurate motor temperature monitoring. This monitoring is controlled by parameter C0594.

x091

EEr External monitoring (activated via DCTRL)

An external monitoring function has triggered this fault, which is activated via DCTRL (Drive Control) and configured through parameter C0581. The 'x' in the code indicates the response type: 0 for TRIP, 1 for message, 2 for warning.

x110

H10 Thermal sensor error at heatsink

An error has been detected with the thermal sensor responsible for monitoring the heatsink temperature. This indicates a fault with the sensor itself or its wiring, compromising the heatsink temperature monitoring. This monitoring is controlled by parameter C0588.

x111

H11 (Temperature sensor error: Temperature inside the controller)

The internal temperature sensor within the controller is reporting undefined values. This compromises the ability of the drive to monitor and protect itself against overheating conditions.

x166

CAN Sync Telegram Error

An incorrect transmission of the synchronization telegram (displayed as P16) has occurred on the CAN system bus. This internal fault, related to C1290, indicates an issue with the timing or integrity of CAN communication synchronization, which can lead to unstable multi-axis operation.

x200

NMAX (Maximum system speed exceeded)

The maximum system speed (defined by C0596) has been exceeded. This typically occurs due to an excessively high active load, such as in hoist applications, or if the drive is not speed-controlled and torque limits are too low, allowing overspeed.

x220

CDA

An attempt was made to transmit profile data that was detected as faulty. This typically occurs during communication processes involving profile data transfer, indicating data integrity issues.

x221

CDA-LOAD

A checksum error was detected for the transferred profile data, indicating corruption or an incomplete transfer. This means the integrity of the loaded profile data is compromised and may lead to incorrect operation.

x240

ovrTrans Queue

The transmit request memory has overflowed, indicating too many CAN objects are queued for transmission. This can lead to delays or loss of communication on the system bus.

x241

ovr Receive

Too many receive telegrams are present on the system bus (CAN). This overload can cause issues with processing incoming communication data, potentially leading to lost messages or communication delays.

x250

2.Flash Err

An error occurred during access to the FLASH memory, indicating the PLC program attempted to access non-available or defective memory. This could signify a hardware issue with the FLASH memory module, preventing proper program execution or data storage.

x251

AddData CsErr

A checksum error occurred when loading data into the FLASH memory. This indicates data corruption during the transfer process to non-volatile memory, which can lead to incorrect program behavior or lost settings.