Abs Encoder 2
Indramat · ServoDyn D Servo Drive
What does 25 mean?
This error occurs if the absolute encoder for Axis 2 is not properly connected, or if data transmission between the encoder and the CLM01.3-M is interrupted or corrupted. This prevents the system from obtaining an absolute position reference for Axis 2.
Common Causes
- Absolute encoder cable for Axis 2 is disconnected, damaged, or incorrectly wired (to CLM01.3-M connector X2).
- Data transmission error from the absolute encoder to the CLM01.3-M.
- Defective Axis 2 absolute encoder.
- Incorrect Encoder Data A2 parameter (P41) setting for the type of absolute encoder used.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify that Parameter P41 (Encoder Data A2) for Axis 2 correctly matches the specifications of the installed absolute encoder.
- 2
Inspect the physical connections of the absolute encoder cable to both the Axis 2 motor and CLM01.3-M connector X2 for secure and correct wiring.
- 3
Check the absolute encoder cable for any signs of damage, fraying, or loose shielding.
- 4
Test the absolute encoder for proper operation, potentially by checking its output signals if diagnostic tools are available.
- 5
If the error persists after thorough checks, consider replacing the absolute encoder or its cable.