Error during phase progression
Indramat · Indradrive
What does F4004 mean?
The communication between the IndraDrive and its master controller failed to progress to the next expected communication phase. This indicates a stall or failure in advancing through the required communication states (e.g., from phase 0 to 1, or 1 to 2), preventing operational mode.
Common Causes
- Master controller not issuing the correct phase progression commands.
- Drive not acknowledging phase change requests.
- Communication bus issues (e.g., noise, cable damage) preventing reliable phase negotiation.
- Incorrect communication parameters in either the master or slave.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify the configuration of the master controller to ensure it is correctly managing the communication phase progression.
- 2
Inspect the communication cable and connections for any physical damage or loose contacts.
- 3
Check for any errors or warnings on the master controller that might indicate communication issues.
- 4
Review the IndraDrive's communication parameters (e.g., bus address, baud rate) to ensure they are correct.
- 5
If applicable, use a bus analyzer tool to monitor communication traffic and identify the exact point of failure in phase progression.