Invalid addressing actual value data container A
Indramat · IndraDrive MPx02
What does E4009 mean?
An error occurred during the index check in the multiplex channel of the IndraDrive MPx02. During cyclic data exchange, the index used to access "Data container A: configuration list actual value-x" points to a non-initialized position in the list, leading to issues with reading actual values.
Common Causes
- Incorrect configuration of "Data container A: configuration list actual value-x"; the list may not be properly sized or initialized.
- An invalid index or address in the high byte of S-0-0368 (Data container A: addressing) is attempting to access uninitialized memory.
- Corruption of data container A's configuration list for actual values.
- Logic error in the master controller or internal drive program attempting to read from an invalid address.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Check the configuration settings for "Data container A: configuration list actual value-x" in the IndraDrive MPx02 to ensure it is properly initialized and contains valid data.
- 2
Verify the high byte of parameter S-0-0368 (Data container A: addressing) to ensure it is pointing to a valid, initialized position within the data container.
- 3
Review the application logic that reads from "Data container A" via the multiplex channel for any out-of-bounds addressing attempts.
- 4
Consult the functional description of the firmware for "Multiplex Channel" for detailed information on proper configuration and addressing of data containers.
- 5
Perform a drive reset and re-download the configuration if data corruption is suspected.