Validation error of safety related operating mode
Indramat · IndraDrive MPx02
What does E3105 mean?
The IndraDrive MPx02's integrated safety function has detected an invalid or inconsistent configuration for a safety-related operating mode (e.g., Safely Limited Speed, Safe Operating Stop). This prevents the drive from entering a verified safe mode, indicating a potential safety risk and requiring re-configuration.
Common Causes
- The selected safety-related operating mode is not configured correctly or completely.
- A conflict exists between different safety function settings or parameters.
- Parameters defining the operating mode have been corrupted or improperly modified.
- The requested safety-related operating mode is not supported by the current safety configuration or firmware version.
- Incorrect sequence of activation for safety operating modes.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Using the safety configuration tool, review the settings for all safety-related operating modes to ensure they are correctly defined and do not conflict.
- 2
Verify that the parameters for the specific safety-related operating mode intended for use are valid and match the machine's safety concept.
- 3
Perform a re-validation of the entire safety configuration after any parameter changes.
- 4
Check for any firmware updates or compatibility requirements for the safety module and the drive's main firmware.
- 5
If the error persists, conduct a thorough review of the machine's safety concept and the drive's safety configuration, then contact Indramat safety service.