Mains failure
Indramat · CLM01.3-M Flying Cutoff Control
What does F381 mean?
With HVR power supply units only! At least one phase of the 3-phase power supply input to the HVR unit is missing, indicating a loss of input power.
Common Causes
- At least one phase of the 3-phase power supply input to the HVR unit is missing.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify the incoming 3-phase power supply at the input terminals of the Indramat HVR power supply unit (X1/L1, X1/L2, X1/L3) using a multimeter. Confirm all three phases are present and balanced.
- 2
Inspect all upstream mains fuses and circuit breakers for the power supply unit. Replace any blown fuses or reset tripped breakers.
- 3
Check power contactors and their auxiliary contacts for proper operation and engagement in the power distribution circuit.
- 4
Inspect all power wiring connections from the mains supply to the HVR unit for looseness, damage, or disconnections.