F245

Encoder 2 failure: quadrant error

Indramat · CLM01.3-M Flying Cutoff Control

What does F245 mean?

The evaluation of the additional optional encoder (encoder 2) is active. A plausibility check between the sinusoidal input signals of the optional encoder and the counter fed by these signals has failed, indicating an error in the encoder feedback.

Common Causes

  • Defective encoder cable for encoder 2.
  • Disruptive electromagnetic interference on the encoder cable for encoder 2.
  • Defective encoder interface in the Indramat DIAX04 SSE-03VRS drive controller or the encoder itself.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    De-energize the system. Inspect the encoder 2 cable for physical damage, kinks, and proper connection at both the motor encoder and the Indramat DIAX04 SSE-03VRS drive controller.

  2. 2

    Verify the shield continuity and proper grounding of the encoder cable. Ensure the cable is routed separately from power cables to minimize electromagnetic interference.

  3. 3

    Test the individual signal lines (e.g., A, /A, B, /B) of the encoder cable for continuity and short circuits. Check the sine/cosine signals at the drive input for proper waveform and amplitude using an oscilloscope if possible.

  4. 4

    If the cable and external connections are verified as good, the encoder itself might be defective, or the encoder interface within the Indramat DIAX04 SSE-03VRS drive controller may be faulty. Prepare for replacement of the encoder or the drive controller.

Browse all codes in this manual (31)
Verified technical data. Last updated: March 2026

Related Faults

Source: Indramat CLM01.3-M Flying Cutoff Control
Indramat F245 — Fixing: Encoder 2 failure: quadrant error T… | ErrorLib