Pulsecoder Serial Data Error
Fanuc · R-30iB Mate + Mate Plus Robot
What does SRVO-068 mean?
The serial Pulsecoder fails to return serial data in response to a request signal. This indicates a communication fault between the servo amplifier and the Pulsecoder, potentially due to loose connections, damaged cabling, or a faulty Pulsecoder itself.
Common Causes
- Interruption in serial communication between the servo controller and pulsecoder.
- Damaged pulsecoder serial data cable or connectors.
- Faulty pulsecoder unit reporting invalid serial data.
- Noise interference on the serial communication lines (e.g., P1-31, P1-32).
- Incorrect pulsecoder communication protocol settings.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Ensure the robot connection cable (RMP1, RP1) connector (CRF8) on the 6-Axis servo amplifier and the connector on the motor side are tightly connected.
- 2
Check that the shielding of the robot connection cable (RMP1, RP1) is securely grounded in the cabinet.
- 3
Replace the Pulsecoder.
- 4
Replace the servo amplifier.
- 5
Replace the robot connection cable (RMP1, RP1, RM1).
- 6
Replace the internal cable of the robot (for the Pulsecoder, or for the Motor).