ALARM 2

Live zero error

Danfoss · VLT HVAC Drive High Power

What does ALARM 2 mean?

The signal on one of the analog inputs is less than 50% of the programmed minimum value. This condition, appearing if parameter 6-01 Live Zero Timeout Function is programmed, often indicates broken wiring or a faulty sensor/device sending the analog signal, risking incorrect operation or control.

Common Causes

  • Broken wire or loose connection in the analog input signal path (e.g., between sensor and AI terminal 53).
  • Sensor failure, providing an output signal below its specified live zero threshold (e.g., 4-20mA signal dropping below 2mA).
  • Incorrect scaling of the analog input in parameter 6-10 (Low Reference) or 6-11 (High Reference), leading to misinterpretation of a low signal.
  • External electrical noise interfering with the low-level analog signal, causing spurious readings.
  • Faulty analog input module on the frequency converter's control board.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the analog input signal at the sensor output terminals using a multimeter (e.g., set to mA or VDC).

  2. 2

    Measure the analog input signal directly at the frequency converter's input terminals (e.g., terminal 53 to 55) to confirm signal presence.

  3. 3

    Inspect wiring for continuity and secure connections from the sensor to the frequency converter's analog input terminals.

  4. 4

    Check parameter 6-01 (Live Zero Timeout Function) to ensure it is correctly configured for the sensor type and application.

  5. 5

    Review parameter 6-10 (Low Reference) and 6-11 (High Reference) settings to accurately match the sensor's output range.

  6. 6

    Replace the analog input sensor if its output consistently remains below the expected live zero despite proper wiring.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults

Source: Danfoss VLT HVAC Drive High Power