Safe Stop activated
Danfoss · VLT HVAC Drive FC 102
What does 68 mean?
The Safe Stop function has been activated, bringing the motor to a controlled stop and preventing unintended restart. This is a critical safety feature typically triggered by an external safety input. The drive will remain in this state until the safety input is cleared and a reset commanded.
Common Causes
- External safety circuit device (e.g., emergency stop button, light curtain, safety gate switch) has been activated.
- Faulty wiring or short circuit in the external Safe Torque Off (STO) or Safe Stop input (e.g., terminals 37, 38).
- Internal safety relay failure or component malfunction within the drive's safety circuit.
- Momentary power sag causing transient activation of the safety input monitoring circuit.
Repair Steps & Checklist
Click steps to track your progress.
- 1
1. Verify the status of all connected external safety devices (e.g., E-Stop, safety mats, light curtains) are reset and active.
- 2
2. Measure the voltage across the Safe Stop input terminals (e.g., 37 and 38) to confirm expected safety circuit status.
- 3
3. Inspect wiring for the Safe Stop circuit for damage, loose connections, or incorrect termination.
- 4
4. Cycle power to the drive and attempt to reset the fault through the LCP or via the external safety reset input.