57

AMA internal fault

Danfoss · VLT HVAC Drive FC 102

What does 57 mean?

An internal fault occurred during the Automatic Motor Adaptation (AMA) process. This indicates a problem within the drive's control logic or measurement system during motor characterization. Repeated attempts could overheat the motor, and the underlying fault needs to be addressed.

Common Causes

  • Component failure on the drive's control board affecting internal current or voltage measurement during AMA.
  • Firmware anomaly or bug within the AMA algorithm that triggers an unhandled internal error.
  • Corrupted parameter settings in the drive's non-volatile memory impacting the internal AMA logic.
  • Faulty internal sensor (e.g., current sensor) leading to inaccurate feedback during motor characterization.
  • Transient power disturbance or electrical noise affecting the drive's internal calculations during the AMA sequence.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Perform a controlled power cycle of the frequency converter, wait at least 30 seconds, and attempt AMA again.

  2. 2

    Initialize the drive to factory default settings (P14-22 Load Parameters), re-enter all motor data, and retry AMA.

  3. 3

    Check the drive's event log (P15-30 Fault Log) for any preceding or co-occurring faults that might indicate a hardware issue.

  4. 4

    Inspect the control card for any visible signs of damage such as burnt components, swelling capacitors, or loose connectors.

  5. 5

    If the fault persists after multiple attempts and resets, consider replacing the control card or the entire drive.

Browse all codes in this manual (75)
Verified technical data. Last updated: March 2026

Related Faults

Source: Danfoss VLT HVAC Drive FC 102