38.1300

Internal Fault: Option software in slot B too old

Danfoss · VLT HVAC Drive FC 102

What does 38.1300 mean?

The software version on the option card installed in slot B is detected as being outdated or incompatible with the frequency converter's current firmware. This mismatch can lead to communication errors, incorrect functionality, or complete failure of the option card.

Common Causes

  • Firmware update of the main frequency converter without a corresponding update for the option card in slot B.
  • Installation of an older generation option card into a drive running current or newer firmware.
  • Incorrect option card firmware package selected or uploaded during a previous update attempt for slot B.
  • Corrupted firmware on the option card in slot B preventing proper version identification by the main drive.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Identify the exact model and current firmware version of the frequency converter via the LCP (e.g., parameter 15-00) or manufacturer software.

  2. 2

    2. Identify the exact model and part number of the option card installed in slot B.

  3. 3

    3. Download the latest compatible firmware for the option card in slot B from the manufacturer's website, ensuring it is compatible with the drive's current firmware.

  4. 4

    4. Connect a laptop to the frequency converter using the appropriate interface (e.g., USB, Ethernet) and use the manufacturer's software to update the firmware of the option card in slot B.

  5. 5

    5. After the firmware update, cycle power to the frequency converter and verify the option card's status and recognized version in parameter group 15-XX (Option Card Info).

Browse all codes in this manual (75)
Verified technical data. Last updated: March 2026

Related Faults

Source: Danfoss VLT HVAC Drive FC 102