AMA low Inom
Danfoss · VLT HVAC Basic FC 101
What does ALARM 52 mean?
The motor current detected during the Automatic Motor Adaptation (AMA) process is too low. This usually indicates an incorrect motor current setting in the parameters or an issue with the motor connection itself, hindering proper parameter identification.
Common Causes
- Motor nominal current (P1-21) set too high in parameters relative to the actual motor nameplate current.
- Open phase or high resistance connection in one or more motor phases (U, V, W) at the drive or motor side.
- Internal short circuit or winding damage within the motor, causing reduced current draw or imbalance.
- Incorrect motor sizing (motor is too small) for the frequency converter's minimum current sensing range.
- Output current measurement circuit fault within the frequency converter itself.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify the motor nominal current (P1-21) matches the motor nameplate data accurately.
- 2
Measure the resistance between motor phases U-V, V-W, W-U at the motor terminals; they should be balanced.
- 3
Check all motor output terminals (U, V, W) for loose connections, corrosion, or damaged wiring.
- 4
Perform an insulation resistance test (Megger test) on the motor windings to ground and phase-to-phase.
- 5
If accessible, measure the motor phase currents (on U, V, W) during a basic V/Hz run to observe current draw.