Option fault
Danfoss · VLT AutomationDrive FC 301/302
What does 35 mean?
An option alarm is received, specific to the option. This is most likely caused by a power-up or a communication fault affecting the option card.
Common Causes
- Incorrect seating of the option card in its designated slot (e.g., Slot A) causing intermittent electrical contact.
- Communication protocol mismatch between the drive's main control board and the installed option card.
- External 24VDC supply (if applicable) to the option card is unstable or below the minimum threshold (e.g., <21VDC).
- Damaged data lines (e.g., RS485, CAN) on the option card's connector pins leading to data corruption.
- Firmware incompatibility between the option card and the main drive controller (e.g., drive FW 3.20 vs. option FW 1.05).
Repair Steps & Checklist
Click steps to track your progress.
- 1
1. Power down the drive completely and disconnect all input power (L1, L2, L3).
- 2
2. Carefully reseat the option card in its designated slot (e.g., Slot A), ensuring it is fully inserted and latched.
- 3
3. Verify the drive's main firmware version (P15-05) and the option card's firmware version (P15-06) using the drive's LCP (Local Control Panel).
- 4
4. Measure the 24VDC supply voltage at the option card's dedicated power terminals (e.g., X32/1, X32/2) with a multimeter to ensure it is within specified limits (e.g., 22-26VDC).
- 5
5. Inspect the option card's connector pins and the drive's slot connector for any signs of physical damage, bent pins, or foreign debris.