Persistent, continuous flashing

K-bus EMC Problems

Beckhoff · CX2100-0914 Embedded PC

What does Persistent, continuous flashing mean?

The K-bus ERR LED flashes continuously, indicating electromagnetic compatibility (EMC) issues within the system. This condition can be caused by undervoltage or overvoltage peaks in the power supply, disrupting stable K-bus operation.

Common Causes

  • Electromagnetic interference on the K-bus communication lines.
  • Poor shielding or grounding of K-bus cables.
  • High noise levels in the industrial environment affecting data integrity.
  • Faulty K-bus interface hardware.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the power supply for undervoltage or overvoltage peaks at the CX2100-0914 unit's input.

  2. 2

    Implement appropriate EMC measures, such as proper grounding and shielding, to minimize electromagnetic interference.

  3. 3

    Perform a restart of the power supply unit by switching it off and then on again to clear the K-bus error state.

Browse all codes in this manual (19)
Verified technical data. Last updated: March 2026

Related Faults