10337

I3 Flash Failed

Allen-Bradley · PowerFlex 750

What does 10337 mean?

An attempt to flash the FPGA configuration device on port 3 has failed. This indicates a problem with the firmware update process, potentially leaving the device in an inoperable state.

Common Causes

  • Corrupted firmware image file or incomplete download interrupting the flash process to Port 3.
  • Transient power supply interruption to the FPGA module (Port 3) or control board during the firmware update.
  • Internal hardware fault within the FPGA device or its associated memory on Port 3 preventing successful write operations.
  • Incompatibility between the selected firmware version and the specific hardware revision of the FPGA on Port 3.
  • Data communication error (e.g., CRC mismatch) during the flash programming process to Port 3.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the integrity of the firmware image file using a checksum utility before attempting re-flash for Port 3.

  2. 2

    Ensure a stable 24VDC control power supply to the drive control board and any external flashing tool for Port 3 throughout the update procedure.

  3. 3

    Attempt to re-flash the FPGA on Port 3 using a known-good firmware file and the manufacturer's recommended programming utility.

  4. 4

    Check diagnostic LEDs on the FPGA module or control board (Port 3) for specific error codes or patterns during a flash attempt.

  5. 5

    If the flash continues to fail, consider replacing the FPGA module or the entire control board associated with Port 3.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults

Source: Allen-Bradley PowerFlex 750