40
Phase W to Ground Fault
Allen-Bradley · PowerFlex 700
What does 40 mean?
A phase-to-ground fault has been detected between the drive and motor on output phase W. This indicates a severe insulation breakdown or short circuit between phase W and earth ground, posing a safety hazard and risk of equipment damage.
Common Causes
- Short circuit detected between Phase W and ground.
- Damaged insulation on Phase W motor winding.
- Faulty Phase W output cable connection to ground.
- Ground fault within the drive's output circuitry for Phase W.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Check the wiring between the drive output terminal W and the motor for a grounded condition.
- 2
Check the motor winding for a grounded condition on phase W.
- 3
Replace the drive if wiring and motor are verified good.
Verified technical data. Last updated: March 2026