What does 39 mean?

A phase-to-ground fault has been detected between the drive and motor on output phase V. This indicates a severe insulation breakdown or short circuit between phase V and earth ground, posing a safety hazard and risk of equipment damage.

Common Causes

  • Short circuit detected between Phase V and ground.
  • Damaged insulation on Phase V motor winding.
  • Faulty Phase V output cable connection to ground.
  • Ground fault within the drive's output circuitry for Phase V.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the wiring between the drive output terminal V and the motor for a grounded condition.

  2. 2

    Check the motor winding for a grounded condition on phase V.

  3. 3

    Replace the drive if wiring and motor are verified good.