F105

C Connect Err

Allen-Bradley · PowerFlex 520-series Adjustable Frequency

What does F105 mean?

The control module was detected to be disconnected from the power module while power was still applied to the drive. This "hot-swapping" action can lead to parameter corruption, damage to the control module, or damage to the power module due to sudden power cycling of sensitive electronics.

Common Causes

  • The control module was removed or became dislodged from the power module while mains power (e.g., L1, L2, L3) was still applied to the drive.
  • Vibration or mechanical shock caused the control module to momentarily lose connection with the power module during operation.
  • Loose or damaged connectors between the control module and the power module, leading to intermittent contact.
  • Internal failure of the power module or control module detection circuitry.
  • Incorrect reassembly after maintenance, where the control module was not fully seated before applying power.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. COMPLETELY remove all mains and control power from the drive (e.g., 24VDC) for at least 5 minutes to allow internal capacitors to discharge.

  2. 2

    2. Power down the drive, then firmly push the control module into the power module until it is fully seated and secured (e.g., using retaining clips).

  3. 3

    3. Inspect the module interconnect pins and sockets between the control and power modules for bent pins, debris, or corrosion.

  4. 4

    4. Apply power to the drive, then check for any other faults that may indicate physical damage from the previous "hot-swap" event.

  5. 5

    5. If the fault persists, attempt to swap the control module with a known good one (if available) to isolate the faulty component.

Browse all codes in this manual (48)
Verified technical data. Last updated: March 2026

Related Faults

Source: Allen-Bradley PowerFlex 520-series Adjustable Frequency