F39

Motor Phase V to Ground Fault

Allen-Bradley · PowerFlex 40 Adjustable Frequency

What does F39 mean?

This fault indicates a grounded condition on motor phase V (output terminal V) between the drive and the motor. This usually points to insulation breakdown in the motor winding or the connecting cable.

Common Causes

  • Insulation breakdown of motor winding for phase V to the motor frame due to aging, overheating, or moisture.
  • Damage to the motor cable insulation for phase V conductor, creating a short to ground (e.g., pinch point, abrasion).
  • Moisture or conductive debris accumulation within the motor terminal box specifically affecting phase V connection.
  • Loose or improperly terminated wiring for phase V at the motor or drive terminal, contacting the grounded enclosure.
  • Internal drive output stage component failure (e.g., IGBT) specifically related to the V phase output.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect motor cables (U, V, W) from drive output terminals. Perform an insulation resistance test (megger) from motor cable phase V conductor to ground.

  2. 2

    Perform an insulation resistance test (megger) from the motor winding phase V terminal to the motor frame (ground) with other phases isolated.

  3. 3

    Visually inspect the motor cable for phase V for any signs of physical damage, cuts, or abrasion along its entire length.

  4. 4

    Inspect the motor terminal box and the drive output terminal for phase V for loose strands, moisture, or conductive material causing a short to ground.

  5. 5

    Check the resistance between the motor terminals U, V, W with a multimeter; a significant imbalance or near-short on phase V might indicate a winding fault.

Browse all codes in this manual (26)
Verified technical data. Last updated: March 2026

Related Faults

Source: Allen-Bradley PowerFlex 40 Adjustable Frequency