F48

Params Defaulted

Allen-Bradley · PowerFlex 4 Adjustable Frequency

What does F48 mean?

This fault indicates that the drive has either been commanded to restore factory default values to its EEPROM, or a corruption of parameter data occurred spontaneously. This resets all configurable parameters.

Common Causes

  • Power loss or incorrect parameter save operation.
  • Factory reset or parameter initialization performed.
  • EEPROM or memory corruption affecting parameter storage.
  • Parameter load failure from external source.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Clear the fault by pressing the Stop key, cycling power to the drive, or setting parameter A100 [Fault Clear] to option 1 ('Reset Fault') or 2 ('Clear Buffer').

  2. 2

    Reprogram all necessary drive parameters to their application-specific values after the defaults have been written.

Browse all codes in this manual (24)
Verified technical data. Last updated: March 2026

Related Faults

Source: Allen-Bradley PowerFlex 4 Adjustable Frequency