FF39

->POWEROFF!

ABB · ACS800

What does FF39 mean?

This alarm indicates that the inverter type (e.g., sr0025_3) of the ABB ACS800 drive has been changed, usually at the factory or during drive implementation. It requires a complete control board power cycle to validate the new configuration and apply the changes. This fault typically activates after an 'HW RECONF RQ' (FF38) alarm.

Common Causes

  • An inverter type change has been detected, and the system requires a power cycle to apply and validate the new hardware configuration in the drive.
  • New hardware components requiring re-initialization have been installed or configured.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Ensure all necessary actions related to the preceding 'HW RECONF RQ' (FF38) alarm have been performed.

  2. 2

    Switch the control board power of the ABB ACS800 drive off completely using the main disconnect switch.

  3. 3

    Power on the control board again to allow the drive to validate the inverter type change and complete its internal hardware reconfiguration.

  4. 4

    Confirm that the fault clears and the drive operates normally after the power cycle, and verify the inverter type shown in drive parameters matches the physical unit.

Browse all codes in this manual (33)
Verified technical data. Last updated: March 2026

Related Faults

ABB FF39 — How to resolve: ->POWEROFF! | ErrorLib