E4-9770

No Communication with Hot Swap Terminal Unit

ABB · System

What does E4-9770 mean?

Communication with the hot swap terminal unit has been lost. This can be due to a temporary glitch or a hardware failure in the terminal unit or its communication path, affecting all I/O modules connected to it. This can lead to loss of I/O control.

Common Causes

  • Loose or faulty backplane connection between the controller/adapter and the hot swap terminal unit.
  • Damaged communication lines or connectors on the backplane itself (e.g., bent pins, corrosion).
  • Interruption or instability of the power supply (e.g., 24VDC) to the hot swap terminal unit.
  • Severe Electromagnetic Interference (EMI) disrupting the high-speed data communication on the backplane.
  • Firmware error or lock-up condition within the hot swap terminal unit preventing communication response.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Reseat the hot swap terminal unit firmly in its slot, ensuring all backplane connectors are fully engaged.

  2. 2

    2. Verify the power supply voltage (e.g., 24VDC) at the terminal unit's input terminals using a multimeter.

  3. 3

    3. Inspect the backplane bus connectors for bent pins, corrosion, or foreign debris that could impede communication.

  4. 4

    4. Check the grounding connections for the entire I/O rack and the hot swap terminal unit.

  5. 5

    5. Perform a controlled power cycle of the I/O rack or the entire control system to reset communication.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults