25
Channel stuck-at error
ABB · PB610 Panel Builder 600 Programming Software
What does 25 mean?
A safety I/O channel is detected to be 'stuck' in a fixed state (e.g., permanently ON or OFF) and does not respond to changes as expected. This suggests a potential internal fault within the I/O module or an external wiring issue causing the channel to be latched. This is a severity 3 error.
Common Causes
- Analog input channel is not changing its value.
- Sensor connected to the channel is stuck.
- Fault in the analog-to-digital converter (ADC).
- Configuration error for the input channel.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Check the wiring connected to the I/O module channel for any shorts to power, ground, or open circuits.
- 2
Perform a restart of the I/O module to reset its internal state.
- 3
If the error persists after verifying wiring and restart, replace the I/O module.
Verified technical data. Last updated: March 2026