A2B3

Earth leakage

ABB · ACS880

What does A2B3 mean?

The drive generates a warning when an earth fault or current unbalance is detected in the motor or motor cable. This indicates a potential insulation degradation or leakage current to ground, which requires investigation to prevent a full fault trip or safety hazard.

Common Causes

  • Degradation of insulation in the motor cable (e.g., due to aging, moisture, mechanical abrasion) leading to leakage current to ground.
  • Moisture ingress or contamination (e.g., oil, conductive dust) at the motor terminal box or cable glands.
  • Partial insulation breakdown within the motor windings, allowing small currents to flow to the motor frame (earth).
  • Improper grounding of the motor frame or the drive, creating an undesired earth path or ground loop.
  • High frequency common mode currents finding a path to ground through the motor cable shielding due to poor EMC installation.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Disconnect the motor cable from the drive. Perform an insulation resistance test (Megger, e.g., 500VDC) on each motor phase cable (U, V, W) to ground (PE).

  2. 2

    2. Inspect the motor terminal box for signs of moisture, corrosion, or contamination and ensure all cable glands are properly sealed.

  3. 3

    3. Inspect the entire length of the motor cable for visible damage to the outer jacket or signs of wear.

  4. 4

    4. Verify the integrity of the ground connection from the motor frame to the machine frame and back to the drive's PE terminal.

  5. 5

    5. Check for proper termination of the motor cable shield at both the drive and motor ends, ensuring it is grounded correctly.

Browse all codes in this manual (116)
Verified technical data. Last updated: March 2026

Related Faults

ABB A2B3 (Earth leakage) — ErrorLib Technical Library | ErrorLib