10040

Hiperface DSL encoder error

ABB · ACS850 Standard Program Firmware

What does 10040 mean?

An error has occurred while attempting to read position data over the Hiperface DSL interface. This suggests a problem with the feedback device wiring, the motor connector, or connections inside the adapter, which can lead to inaccurate or lost position information, affecting motor control and synchronization.

Common Causes

  • Hiperface DSL cable damage (e.g., open circuit, short circuit) between the motor and the drive's encoder input connector (e.g., X14).
  • Improper termination or insufficient shielding on the Hiperface DSL cable, causing communication errors due to electromagnetic interference (EMI).
  • Faulty Hiperface DSL encoder embedded within the motor, preventing data transmission or providing corrupted data.
  • Incorrect wiring of the Hiperface DSL cable at the drive's X14 connector (e.g., data+ / data- lines swapped, power lines incorrect).
  • Drive's encoder interface module (if applicable) is faulty or not correctly configured for Hiperface DSL protocol (e.g., P5-01 setting).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Power down the drive, then visually inspect the Hiperface DSL cable for any physical damage or stress points along its length.

  2. 2

    Using a multimeter, test for continuity and isolation between individual conductors of the Hiperface DSL cable.

  3. 3

    Verify the Hiperface DSL cable's shielding is properly connected to ground at both the motor and the drive end (e.g., X14 terminal ground).

  4. 4

    Confirm the Hiperface DSL cable wiring at the drive's X14 connector strictly follows the manufacturer's connection diagram (e.g., data+, data-, 24VDC, GND).

  5. 5

    Check the drive's encoder configuration parameter (e.g., P5-01) to ensure 'Hiperface DSL' is correctly selected as the feedback type.

  6. 6

    Monitor the drive's diagnostic parameters for encoder status (e.g., P5-05, P5-06) to identify specific communication errors or receive frames.

Browse all codes in this manual (57)
Verified technical data. Last updated: March 2026

Related Faults

Source: ABB ACS850 Standard Program Firmware