Multi-Function Input (H1-xx) Conflict
Yaskawa · V1000
Was bedeutet oPE03 ?
A contradictory setting has been assigned to one or more of the multi-function digital inputs (H1-01 through H1-06). This includes assigning the same function to multiple inputs (except 'External fault' and 'Not used'), setting incompatible functions, or configuring functions without their required counterparts, leading to control logic conflicts.
Häufige Ursachen
- Two or more multi-function digital input parameters (H1-01 to H1-06) are set to the exact same function (e.g., 'Run Forward') where this is not permitted.
- A function that requires a unique input (e.g., 'Reset Fault') has been assigned to more than one input parameter.
- Incorrect parameter group uploaded from another system where input assignments differ.
- User error during manual configuration, leading to an unintended duplication of input functions.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Access parameters H1-01 through H1-06 (Multi-Function Digital Inputs) via the drive's keypad or software.
- 2
2. Review the function assignments for each input parameter (H1-01 to H1-06) to identify any duplicate or conflicting settings.
- 3
3. Reassign the conflicting parameter(s) to a unique, unused function or set them to '0' (function disabled) if not required.
- 4
4. Refer to the drive's manual for a list of valid functions and their uniqueness requirements for multi-function inputs.
- 5
5. Perform a drive power cycle after correcting the parameter settings to ensure changes are applied.