Übersetzen...
Ground Fault

Ground Fault

Yaskawa · V1000

Was bedeutet Ground Fault ?

The ground leakage current on the drive's output side has surpassed 50% of the drive's rated output current. This often indicates damaged motor or cable insulation, or excessive stray capacitance due to long cable runs. This condition poses a serious electrical safety hazard and potential damage to the motor or drive.

Häufige Ursachen

  • Damaged insulation on the motor output cables (U, V, W) to ground, potentially due to mechanical abrasion, crushing, or chemical exposure.
  • Internal insulation breakdown within the motor windings (U, V, W phases) to the motor frame (ground) due to overheating or aging.
  • Water ingress or excessive moisture in the motor or terminal box, reducing insulation resistance to ground.
  • Excessive cable length between the drive and motor, leading to high stray capacitance to ground, especially with unshielded cables.
  • Incorrectly terminated or damaged motor cable shield, allowing leakage currents to flow to ground.
  • Drive's ground fault detection sensitivity (e.g., Parameter L2-03) is set too high for the application, especially with multiple motors or long cables.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Power down the drive completely (wait for DC bus discharge). Disconnect all motor leads (U, V, W) from the drive's output terminals.

  2. 2

    2. Perform an insulation resistance test (Megger test at 500-1000VDC) on each motor phase (U, V, W) to the motor frame ground. Reading should be >1MΩ, ideally >100MΩ.

  3. 3

    3. Inspect the entire length of the motor cable for any visible damage to the outer jacket or signs of wear that could compromise insulation.

  4. 4

    4. Measure the insulation resistance of the motor cable from each conductor (U, V, W) to the cable shield/ground.

  5. 5

    5. Verify the motor cable shield is correctly terminated and grounded at both the drive and motor ends. Ensure no stray strands are touching ground.

  6. 6

    6. If the ground fault detection parameter (e.g., L2-03 'Ground Fault Detection Level') is adjustable, slightly reduce its sensitivity if the cable length is excessively long (over 50m) and insulation is verified good.

Alle Codes in diesem Handbuch durchsuchen (87)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes