Übersetzen...
Uv3

Soft Charge Circuit Fault

Yaskawa · P1000

Was bedeutet Uv3 ?

An issue with the drive's internal soft charge circuit has been detected. This circuit manages the initial charging of the DC bus capacitors, preventing high inrush currents.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure input voltage at the drive's L1, L2, L3 terminals to verify it falls within the specified operating range for the Yaskawa P1000.

  2. 2

    Inspect all input power wiring and connections at the drive and upstream breaker for tightness, corrosion, and signs of overheating or physical damage.

  3. 3

    Verify the displayed DC bus voltage on the drive's keypad during power-up attempts to observe the charging behavior before the Uv3 fault triggers.

  4. 4

    Check for the presence and proper connection of any external braking units or regeneration modules, ensuring their wiring to the DC bus terminals is correct and intact.

  5. 5

    Review drive parameters related to undervoltage trip levels, input voltage settings, and power-up sequence delays to confirm correct configuration as per Yaskawa specifications.

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes